Transformer kVA Calculator

Enter voltage, current, and phase to size your transformer in kVA.

How it is calculated

The required apparent power is kVA = V × A ÷ 1000 for a single-phase load and kVA = √3 × V × A ÷ 1000 for a three-phase load, where V is the line voltage in volts and A the load current in amperes. For three-phase, use the line-to-line voltage and the line current. The result is then compared with a built-in list of standard ratings: 1, 1.5, 3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 112.5, 150, 167, 200, 250, 333, 500, 750, 1000, 1500, 2000, 2500, 3000, 3750, 5000, 7500 and 10,000 kVA. The tool shows the smallest standard size that is equal to or above your calculated value. It adds no safety margin or growth allowance, so if the calculation lands exactly on a standard size, you get that size with no spare capacity. Voltage and current must be above zero, and a load above 10,000 kVA gives no result. Anything other than the three-phase option is treated as single-phase.

Worked example

A balanced three-phase load of 250 A at 400 V. Apparent power = 1.732 × 400 × 250 ÷ 1000 = 173.21 kVA. The standard sizes around that figure are 167 kVA, which is too small, and 200 kVA, which is the first one at or above it. The tool shows 200.0 kVA as the next standard size, leaving about 27 kVA (15%) of spare capacity. The same numbers treated as single-phase would give only 100 kVA, which shows why choosing the right phase option matters.

Try this example →

Common mistakes

  • Leaving the phase option on single-phase for a three-phase load. The result is then about 42% too low, because the √3 factor (1.732) is missing.
  • Entering phase voltage instead of line-to-line voltage for a three-phase system. The √3 formula expects the line-to-line voltage, for example 400 V rather than 230 V.
  • Entering a power in kW as if it were kVA. The tool works from volts and amperes, so convert from kW only after dividing by the power factor.
  • Treating the next standard size as a design margin. If your load computes to exactly 50.00 kVA, the next standard size is also 50 kVA; add growth allowance and inrush current yourself.
  • Entering the current of a transformer's primary side with the secondary voltage, or the other way round. Voltage and current must come from the same winding.

About this calculator

Transformers are rated in kVA (kilovolt-amperes) rather than kilowatts because that rating describes apparent power — voltage times current — independent of the load's power factor, which the transformer itself doesn't control. For a single-phase load, kVA = (V × A) ÷ 1,000; for a balanced three-phase load, kVA = (V × A × √3) ÷ 1,000, the √3 ≈ 1.732 factor accounting for the phase relationship between the three conductors.

Electricians and engineers size a transformer to the next standard rating above the calculated requirement — common distribution sizes per ANSI/IEEE C57 include 15, 25, 37.5, 50, 75, 100, 167 and 250 kVA — rather than an exact custom size, both because that's what's stocked and to leave headroom for load growth and inrush current.

Was this helpful?

You can pick up to 3 reactions.

Comments (0)

  • Be the first to comment.

Popular calculators

All Calculators