kVA to Amps Calculator
Enter the values to get the current.
Result
How it is calculated
Apparent power in kVA is multiplied by 1000 to get volt-amperes and divided by the voltage. For a single-phase supply the formula is I = kVA × 1000 / V; for a three-phase supply it is I = kVA × 1000 / (√3 × V), with √3 ≈ 1.732. I is the line current in amperes and V is the voltage in volts: phase-to-neutral for single phase, line-to-line (for example 400 V) for three phase. Phase is single unless three-phase is chosen. The voltage must be above zero and the kVA cannot be negative. The result is rounded to two decimals. Power factor is not an input: kVA already includes it, so the answer is the total current the conductors carry, not only the part doing useful work.
Worked example
A 50 kVA three-phase transformer feeds a 400 V line-to-line supply. Convert to volt-amperes: 50 × 1000 = 50 000 VA. The denominator is √3 × 400 = 692.8. The current is 50 000 / 692.8 = 72.17 A on each phase conductor. If the same 50 kVA were treated as single phase at 400 V, the formula would give 50 000 / 400 = 125.00 A, so choosing the wrong phase setting changes the answer by a factor of 1.73.
Common mistakes
- Leaving the phase on single for a three-phase machine. At 400 V the same 50 kVA gives 125.00 A instead of 72.17 A, so cables and breakers would be sized far too big.
- Using the phase-to-neutral voltage (230 V) in the three-phase formula. The √3 already accounts for the phase relationship, so enter the line-to-line voltage, here 400 V.
- Entering kW instead of kVA. A kW rating is real power; dividing by the power factor gives kVA, and a load at 0.8 power factor draws a quarter more current than the kW figure suggests.
- Typing the power in VA or MVA. The field takes kVA, so 50 000 VA must be entered as 50 and 0.5 MVA as 500.
- Treating the result as a breaker rating. It is the rated full-load current; breakers, cables and starting currents need extra margin and local code rules.
About this calculator
Apparent power in kVA converts to current using I = (kVA × 1000) / V for a single-phase circuit, or I = (kVA × 1000) / (√3 × V) for a balanced three-phase circuit, where V is the line voltage. Because kVA includes both real and reactive power, this current figure is the total the conductor actually carries, not just the power-producing portion.
Electricians and electrical engineers use this conversion to size breakers, cables, and transformers from a generator or transformer's kVA nameplate rating, and to check that a panel's rated current can support the connected load.
Was this helpful?
You can pick up to 3 reactions.
Popular calculators
Loan Calculator
Monthly payment, total interest and full amortization schedule.
Percentage Calculator
Percent change, percent of, and ratio calculations.
Discount Calculator
Calculate final price, savings, and discount amount.
BMI Calculator
Body mass index from height and weight (metric or imperial).
Age Calculator
Compute your exact age in years, months and days from a birth date.
Compound Interest Calculator
Calculate the final amount and interest earned with compounding.
All Calculators
No calculators found
Comments (0)